T&R ART3V-Relay Test System

Part No : 235

Quick Overview

New features - More adaptable

Availability: In stock

£11,781.00

Details

T&R ART3V-Relay Test System


Request Demo 

 

The new ART3V brings new features to our range of relay test equipment making it far more adaptable. The new output voltages are higher and have a finer level of accuracy and control. The new full colour LCD provides more test detail, making it easy to understand. 

The ART3V is ideally suited to testing G59 protection, including loss of mains protection. Vector surge and df/dt (ROCOF) relays can be simply tested and timed, as well as other protection requiring one to three voltages, including:

Under and over frequency relays
Under and over voltage relays
Synchronising relays
df/dt & ROCOF relays
Vector surge relays
Transducers

 

Features:

3-P Voltage output from 1-P supply
0-450V P-N output voltage
20VA/phase maximum output
Variable Frequency 30-999.9Hz
Phase shift ±180.0°
Multi-function timing system
USB keyboard for comment
USB data storage.
Ideally suited to testing G59 schemes
Step change of phase and df/dt
Large 6.5” back-lit colour LCD
Automatic mains voltage selection
Fully Programmable test procedures.
Rugged case and weighs under 9kg.


In conjunction with the ART3C or a current source (such as the 200ADM-P), the ART3V can be used to test protection circuits, including:

Directional relays
Distance protection
Phase angle relays
Power relays
Power transducers

ART3V Specification


Output

The output of the ART3V has 4mm safety sockets for phases A, B, C and neutral. The neutral connection may be omitted for a delta connection. The neutrals can be linked for a star connection using the provided accessory.

Timing System

The timing system on the ART3V is flexible and transparent with different modes of operation.

USB Data

The ART3V can be connected to a USB keyboard for adding comments to tests. Each test is stored to a USB memory key with each comment. The data is stored in a *.CSV format allowing it to be opened in all types of desktop PC spreadsheet software.

Modes of Operation - Output Adjust

This mode allows full control of frequency, voltage and phase.

Phase Lock Mode

The frequency and phase of the output can be controlled by an external reference in phase lock mode. The reference may be the mains supply to the ART3V, an external voltage, current. This mode allows testing of directional and distance protection in conjunction with an external current source.

Fault Config Mode

Fault Config mode allows extra flexibility in testing complex timed events or several sets of values that must be applied to a relay in turn. This mode allows three sets of values to be set in advance (pre-fault, fault, and post-fault values). The ART3V may be set to switch from one state to the next on a change of contact or after a specific time. In addition, the timer may be set to start or stop on any one of the state changes or a change of contact state. This mode allows frequency, phase and voltage to be changed simultaneously if required. Test configurations can be save to USB. More complex configurations can be loaded from the USB, such as a complete G59 relay test, such as relay stability tests.

df/dt and ROCOF (Rate Of Change Of Frequency)

Loss of mains protection often takes the form of a df/dt relay, sensitive to the rate of change of frequency over time. The ART3V is able to generate a swept frequency output with accurate rates of change of frequency between preset frequencies.

 

ART Display

 

Supplied Accessories:


Output lead set
Lead set case
Mains lead
Spare fuse set
Operating manual